ASET logo
[ EdTech'94 Contents ] [ EdTech Confs ]

The built technology of the learning environment

Henrique J Harding
Bestec Pty Ltd


Air conditioning services considerations

Building Engineering Services comprise Mechanical (Air Conditioning), Electrical, Communications, Fire Protection and Vertical Transportation Services and account for between 20% to 35% of the total building cost. However, these operating systems, so important for the day to day functioning of every building account for an even greater percentage of the criticism levelled at today's buildings. In recent times most criticism has arisen from the changes in demand placed on the Building Engineering Services by the explosion in Communications equipment that has occurred in the last 20 years. Educationalists generally do not understand that changes in the teaching and learning process are very dependent upon the quality of Building Engineering Services that support the space they occupy.

Up until recent years learning spaces were generally not air conditioned in Australia because of our moderate climate. The seemingly ever increasing application of electronic communications equipment and a growing sophistication of standards now brings about the air conditioned learning environment. Due to the extended hours of operation of the learning centres, air conditioning designers must focus on economical plant and system selection whilst at the same time ensuring long term low cost reliability and maintainability.

Control of after hours operation, which for a learning facility, means ensuring that systems are designed to allow the closing down of air conditioning serving areas not in use, ensures minimisation of wasteful energy consumption and plant operation. Unlike commercial office buildings, the non-use (after hours) period for learning areas can occur at any time of the day or night.

These considerations impact on the types of systems selected and cause the design process to be somewhat unique when compared to other buildings with fixed periods of constant occupancy. The aim of this presentation is to provide a brief overview of the processes involved in selecting and designing an appropriate air conditioning system to meet the particular requirements of a building and its occupants. The Port Adelaide Campus is used as a specific example of the way in which an air conditioning system is selected in response to the client brief.

System considerations

Irrespective of the ultimate use to which a building will be put, there are a number of factors which must be considered in selecting the most appropriate air conditioning system configuration for a specific building. It is important to gain a broad appreciation of the factors influencing system selection before considering the issues specific to learning facilities. For the designer, the process begins with preliminary architectural plans, developed by the architect in response to the project brief.

A well developed client brief will typically canvas the following issues:

The designer must analyse the thermal characteristics of the building fabric, the building configuration and the issues raised in the client brief to select the most cost effective solution to the building air conditioning requirements. In the instance of the Port Adelaide Campus, the client brief contained a heavy emphasis on flexibility of internal partitioning layouts, the ultimate objective being that the entire building or parts thereof should be capable of being converted to commercial office use at a later date.

Preliminary architectural plans indicated a two level building with significant glazing elements orientated towards north, south, east and west. Such a building envelope requires an air conditioning system which is designed to provide independent temperature control to the areas in close proximity to the glazing elements, known as perimeter zones. The temperature conditions within the areas adjacent to the glazing elements are subject to the influence of the sun which varies depending on seasonal factors and the time of day. Furthermore, the proliferation of computer based teaching potentially results in a situation where a high level of heat output from computer equipment and occupants can be concentrated in particular areas which are also subject to intermittent usage. It was therefore apparent that the air conditioning system would be required to be capable of responding to very dynamic thermal loads imposed by building fabric and the occupancy profile. Additionally, the internal partition layouts will invariably change, determining the need for the air conditioning system to be economically re-configured accordingly.

Air conditioning system types

Whilst it is beyond the scope of this presentation to provide a comprehensive description of all available air conditioning system types, it is instructive to understand the three fundamental types of systems commonly employed.

These are as follows:

The following diagrams illustrate the basic componentry of each of the above system types as follows:

Figure M1

Figure M1: Chilled/Heating Water Systems

Figure M2

Figure M2: Water source heat pump systems

Air conditioning system costs

The initial capital cost of the air conditioning systems previously described falls within the following ranges:

System typeCapital cost range

Chilled/heating water systems$280-$350/sq metre
Water source heat pump systems$220-$280/sq metre
Air cooled reverse cycle systems$160-$220/sq metre

Air conditioning systems typically account for 10% -15% of the total building cost.

Interestingly, life cycle studies recently undertaken for tertiary education facilities favour air conditioning systems with a higher initial capital cost such as chilled water/heating water systems.

Figure M3

Figure M3: Air cooled reverse cycle split system packaged units

Operating costs

Current technology full air conditioning systems typically account for the following outgoings.
Cost of energy = 15%-20% of total owning and operating cost

Technical maintenance = 4%-8% of total owning and operating costs

Typically these percentages translate to energy costs of the order of $10/sq metre -$14/sq metre per annum and technical maintenance costs of the order of $8/sq metre -$12/sq metre per annum, thus totalling $18/sq metre -$26/sq metre per annum.

Port Adelaide Campus air conditioning system

The Port Adelaide Campus site is somewhat unique, being situated adjacent to the Port River, enabling a unique solution to the selection of the air conditioning system type. The strong client desire to obtain a cost effective solution offering a high degree of flexibility and low operating and maintenance costs resulted in the final selection of a water source heat pump system. This type of system was selected because it offered a lower capital cost than a chilled water system and due to the reverse cycle cooling/ heating process it offered efficient use of energy.

The use of water source heat pump system offers energy savings when compared to other systems by virtue of the low condensing temperatures at which the system operates at and the ability of the plant to offset cooling and heating requirements in different parts of the building without the injection of further energy from the thermal plant. The 2 pipe condenser water reticulation system is common for both cooling and heating systems and because of the temperature at which the system operates, insulation of the pipework is not necessary thus removing a high cost and long term maintenance element from the project. As heating and cooling can take place in different units simultaneously, heat is either taken from or rejected to the condenser water system hence making the total system relatively energy efficient.

With a chilled water system' insulated pipework is reticulated to all cooling coils located in fan coil units throughout the building. Heating is achieved by a separate insulated reticulation system circulating hot water from a central boiler to heating coils in the fan coil units. This system requires 4 pipes, all of which are insulated. It also requires substantially more plant room space As previously described water source heat pump systems generally incorporate cooling towers and boilers to maintain the condenser water pipework loop within the range of temperatures over which water cooled air conditioning units can operate.

One of the disadvantages of such systems is that cooling towers require significant space, consume substantial energy to operate and require careful ongoing maintenance associated with water treatment systems to eliminate the risk of Legionella. Significant operating and maintenance costs are also attributable to the operation of heating hot water boilers associated with water source heat pump systems. However, investigation into the seasonal variations in the temperature of the Port River indicated that the river water remains within the temperature range of 8-26 degrees Celsius which satisfies the temperature requirements for a water source heat pump condenser water loop. Thus, by drawing water from the Port River to act as cooling water for the air conditioning system, the necessity to provide a cooling tower and boiler system was eliminated.

With respect to system flexibility, it was evident that any attempt to configure the air conditioning system to meet the requirements of the specific fitout immediately proposed would have the potential to restrict future flexibility. The air conditioning system was therefore designed on a block basis in which the particular thermal requirements determined by the building orientation are satisfied by providing independent perimeter zones served by separate air conditioning units and the remaining internal zones are independently served in each block.

This zoning arrangement is illustrated on the diagram - Figure M4. The air distribution systems were also designed for maximum flexibility by incorporating solid insulated sheet metal main distribution ducts and flexible insulated duct work to each ceiling mounted supply air diffuser. This configuration can accommodate minor partition changes by simply relocating the supply air diffusers to suit the space layout. More significant changes may require additional supply air diffusers to be installed, at relatively minor cost.

Figure M4

Figure M4: Port Adelaide Campus air conditioning zones

Changes to internal layouts may also necessitate re-balancing of the air quantities delivered to each area. However, as the building is served by a large number of relatively small capacity air conditioning units. re-balancing can be achieved in specific areas without adversely affecting the remainder of the building and at relatively minor cost. Furthermore. the return air for all areas is routed back to the plant rooms via the ceiling spaces. As the air is relieved from the occupied space via slots built into the light fittings, no modifications are required to the return air systems in the event of internal planning changes. The water source heat pump air conditioning system was installed at a cost of $228/sq metre.

In summary, we believe that by careful consideration of the client brief and close liaison with the Architect and project team a cost effective and flexible air conditioning solution has been achieved.

Electrical services considerations

Like the rapid changes previously noted with respect to vocational education, the impact of modern technology on Electrical Services systems has been dramatic over the past 15-20 years. The brief for the Port Adelaide Campus required an Electrical Services system capable of meeting both present and future needs at reasonable cost whilst attaining a high level of reliability and maintainability. The solution was not only required to be adaptable for both known teaching and commercial environments, but capable of providing upgrade paths into the future. Prior to examining the systems provided at Port Adelaide, it will be instructive to briefly examine the impact of load growth of Electrical Services systems.

Electrical services trends

Until the late 1970s an overall power supply capacity of 100 watts/sq metre was considered extravagant, with a figure of 70 watts/sq metre being considered typical. With the advent of electronic data processing (EDP) and, more recently, networked desktop personal computers, power densities of up to 150 watts/sq metre are now not considered unusual. This increase is primarily made up of two factors, namely, allowance for provision of a computer load of approximately 300 watts to each workstation contributing about 30 watts/sq metre, and the associated additional air conditioning load imposed by computing of approximately 15 watts/sq metre. In addition to the above, user expectations for close climatic control and rapid attainment of conditions have tended to lead to larger air conditioning unit capacities to achieve the desired performance.

As a result, distribution switchboards have become more spatially demanding due to the increased requirement for power outlets. Until the advent of computer based workstations, it was common practice to provide switchboard capacities to cater for I circuit per 20sq metre of useable floor space. Currently, however, each workstation is generally provided with at least one double GPO for computer use and one for general use, leading to a doubling of previous desirable capacity. Further space is required tor lighting controllers, meters and other ancillary equipment. The above factors combine to a more appropriate design capacity of at least 1 circuit breaker space per 10sq metre of useable floor space. The spatial allocation required for switchboards has therefore increased significantly.

Similarly, due to the increased density of services, the space required tor wiring systems has become a more significant factor in building design and must be considered early in the design process.

With respect to lighting, the fluorescent tube has for many years been. and will continue to be tor the foreseeable future. the dominant lighting source in both commercial and educational office type environments.

Other sources, such as metal halide, mercury vapour, high pressure sodium, extra low voltage and compact fluorescent, have been applied but not generally been successful for a variety of reasons including glare control, capital cost, colour rendition and efficiency.

The major developments in recent years are the introduction of the triphosphor fluorescent tube, with greater efficiency and colour rendition, and the ultra low brightness (ULB) louvre. The latter consists of a grid of deep cell high purity aluminium blades which provide the excellent glare control required for extended working with computer screens whilst achieving high efficiency. However, the greater ceiling depth of 150 mm - 175 mm required for these louvres compared with conventional prismatic diffuser of 100 mm - 125 mm has placed further restraints on building design by increasing the required ceiling to slab height.

Apart from wide acceptance of ULB louvres, the major trend in interior lighting has been toward the incorporation of energy saving controls. These include:

All of the above have application in different areas which must be assessed in each project. For instance, central switching may be appropriate to turn off lights in an office, but may not be acceptable in areas where significant loss of illumination may cause safety or operational problems. As a result, any such control regimes must be carefully considered and agreed with the user groups prior to implementation.

A further rapidly developing area is that of security. As vandalism and commercial espionage becomes more prevalent, the installation of electronic access control is increasingly being included in development briefs. Consideration therefore needs to be given to the impact of traffic routes, lock types, detectors and wiring paths on the building fabric.

Obviously, then, the requirements of Electrical Services equipment and wiring systems play a significant part in the development of building design and require early consideration to ensure adequate provision is made.

Also, as the Electrical Services installation is a significant capital investment, commonly 8 -10% of the overall cost of a facility, it is imperative that functional requirements are addressed at an early stage to ensure that adequate capacities are provided tor expansion into the future.

Power infrastructure

At Port Adelaide, the requirements for the provision of a flexible, reliable, maintainable power supply system were met by a structured approach using readily available components. Main switchboards, of which there are two, are housed in fire rated enclosures and incorporate spare capacity and space for additional equipment if required.

Submains cables to the various load centres are run on well defined routes on cable tray in the accessible ceiling space of the ground floor to serve both floors of the two storey building. All submains incorporate at least 25% spare capacity above known requirements and utilise less than 50% of the installed cable tray space.

The submain cables feed miniature circuit breaker distribution switchboards strategically located, as far as possible, at load centres. The use of circuit breaker protection at these switchboards was adopted to enable rapid restoration of power by non technical personnel in the event of overloading and tripping of a circuit. The initial design of the switchboards incorporated between 25-30% spare space above initial requirements. This allowance proved adequate in most cases as fit-out needs became known. However, in a number of instances, where switchboard capacity was exceeded during fit-out, the incorporation of spare space within the switchboard cupboards proved invaluable, enabling the installation of supplementary switchboards. However, the shortfall in a few isolated instances suggests that 50% spare switchboard space should be strongly considered. In addition, switchboards should be located, as far as possible, in accessible corridor spaces for ease of maintenance and to minimise disruption in teaching spaces.

A further aspect incorporated into the switchboards, to address the safety requirements of the brief, was residual current device, or earth leakage, protection to all general purpose power circuits. This form of protection will interrupt power in the event that persons contact live conductors, causing currents through the body sufficient to kill or seriously injure, but not necessarily operate a conventional circuit breaker.

By way of illustration, figure E-1 demonstrates in simplified form, the principle of the design utilised at Port Adelaide. As can be seen, the system is simple in concept. The result, however, is great reliability and flexibility due, in no small part to the spare capacity and accessible installation methods used.

Workstation cabling

Whether catering for a commercial or educational environment, power delivery systems must be both reliable and as flexible as possible. This aspect was stipulated in the brief for the Port Adelaide campus.

To assist in reliability in the information technology environment, all computer workstations and peripherals are provided with power on dedicated cables which supply no other type of equipment.

Thus, the electrical disturbances caused by the operation of equipment such as photocopiers and microwaves are isolated, as far as possible, from effecting computing devices. All power outlets intended for computer only use are distinctly identified to reduce the risk of connection of inappropriate equipment to these circuits.

Figure E-1

Figure E-1: Power reticulation infrastructure block diagram

Being connected by hard wired copper conductor cable and installed by fixing to hard surfaces, only limited flexibility is attainable in consideration of potential power outlet relocation. Accordingly, there will always be some disruption and fabric damage to be repaired when a power installation is altered. However, at Port Adelaide, a conscious decision was taken to install cabling in a manner which would minimise such damage by making relocations as simple as possible.

Many methods have been attempted over the years to solve difficulties in wiring to workstation power and communications outlets. False floors have fallen into disfavour in all but heavily serviced central computing facilities due to high capital costs, increased floor to floor heights, cable management failure, tile damage and limitations in workstation location to avoid supports. The use of ceiling spaces on the floor below and penetrating slabs to workstations is restrictive, disruptive to users, inflexible and. potentially, structurally unsound. In floor ducting, popular in the early 1980s, suffers from cable de-rating due to bunching, restricted access, inflexibility and capital costs.

Accordingly, the approach adopted at Port Adelaide maximises the use of ceiling spaces for wiring, reticulating to workstations via demountable partitions, column conduit access, multiple compartment skirting ducts and integral workstation ducting. Where necessary, service columns are used to drop to workstations located remote from other wiring paths.

As a result, it is relatively simple to access and reposition wiring without major damage.

This aspect was shown to be effective during the fit-out at Port Adelaide, particularly within Block A, where the total function and Electrical requirements changed dramatically. The design solution adopted, although the rework was substantial, enabled rearrangement within a tight time frame and without excessive drama.

Lighting

The lighting installation at Port Adelaide was required to be efficient, flexible, inconspicuous and, in the case of computing suites, low glare. The design solution adopted uses efficient recessed fluorescent luminaires, generally fitted with prismatic diffusers for glare control. As a result of economy measures sought, the use of ultra low brightness luminaires was not possible. Accordingly, where extended computer use was anticipated, silver tinted diffusers were used to reduce glare.

To maximise flexibility, all recessed fluorescent luminaires are connected by flexible cord and plug to facilitate relocation in the event of refurbishment. As compared with hard wired systems, which must be disconnected, relocated and reconnected by an electrician, the flex and plug solution allows unqualified personnel to simply unplug a luminaire, shift it and plug back in. This method is becoming the accepted norm for all commercial interiors.

Similarly, active wiring is taken to all lights rather than merely switchwires. This approach enables switching modifications with only minor rearrangement of wiring in the event of refurbishment or rearrangement.

Access control and intruder detection

As the sophistication of educational facilities increases, so do needs and expectations with respect to building management and comfort systems. One of the most rapidly developing areas is security, incorporating either access control or intruder detection or both.

Access control consists, as the name implies, of means of limiting entry to a facility or portions of the facility. This may be achieved by manual key locking or electric locking. Over the past decade, increases to the perceived threat to facilities due to vandalism, theft, espionage and other nefarious reasons has led to far greater use of electric locking. Control may be achieved by the use of cipher key pads or a variety of different styles of card readers, with different access codes issued for different users, time frames or areas.

The design of any access control system, from the simplest single door controller to the most complex multi level multi user system, must be carefully designed, not only to provide a level of security appropriate to the threat assessment but to ensure that authorised movements through a facility are not unduly impeded. This requires consideration of every controlled point to determine the components and controls needed to best achieve the necessary functions.

Loosely related to access control, intruder detection is provided to generate alarms should unauthorised persons be within or adjacent the secured facility. Devices include movement detectors (passive infrared, ultrasonic, microwave), trip wires, photo-electric beams, glass break detectors and pressure mats. Perimeter door lock tongue sense switches and reed switches. if provided, may be incorporated into the intruder detection system. Control is most commonly by the use of either key switches or cipher key pads. However, interface control with an access control system may also be incorporated if required.

The most recent innovation in intruder detection is the use of closed circuit television video motion detection. Such systems are used for surveillance of selected areas and are configured to record the detection of a change in the field of view, using either video cassette recorders, computer hard disks or both. However, the cost of such systems generally restricts their use to installations with perceived high risk and must be carefully designed to attain maximum cost effectiveness.

At Port Adelaide, access control is achieved by the use of keypad controlled electronically locked doors at focal entries, with other entries being manually locked and alarmed. All spaces with external windows, or accessible from an uncontrolled space, are provided with passive infrared motion detection to detect unauthorised entry. The system as a whole is capable of local configuration for authorised personnel and is remotely monitored.

Summary

The rapid development of and reliance on electronic processing systems and the installation of expensive teaching aids has given rise to dramatic increases in demands on the performance requirements of all Electrical Services facilities in buildings.

Project development must include an early phase for design team consultation to ensure that the final product incorporates sufficient capacity, flexibility and reliability to meet user requirements for many years, thereby avoiding premature obsolescence.

Communications systems considerations

Probably the most rapidly developing area affecting educational facilities in the past decade is the delivery of information technology, supported by the communications systems. The primary communications systems provided to facilities are associated with telephone (including facsimile and modems) and computer traffic. The systems are generally known as voice and data communications respectively. Until recently, both systems were kept rigorously separated and utilised a variety of wiring methods. Before looking at the solution adopted at Port Adelaide, a review of past methods is considered useful in understanding current trends.

Previous systems

As stated above, voice and data systems have historically been run over totally different wiring due to incompatibility of requirements. Voice communications were run on copper conductor cabling utilising both coaxial and twisted pair construction. Terminations were generally by wire wrap or solder tag both of which were cumbersome, space intensive, time consuming and difficult to alter.

Data cabling was also of copper conductor, but used a variety of different constructions, the most common of which are coaxial ethernet and IBM Type I Token Ring. Other vendor specific wiring systems abound, the most important limiting factor being that none was compatible with any other. A further limiting factor was the use of a "plug in" bus system which resulted in protracted total loss of all communications in the event of a breakdown anywhere in the backbone system. A block diagram of a typical bus based system illustrating the effect of cable breakdown is shown at figure C1.

Figure C1

Figure C1: Bus communications cabling

In order to address these problems, the American Electronic Industry Association (EIA) developed the TSB 40 standard which allowed transmission of token ring ethernet, ISDN, video and voice traffic over the same type of cable. This standard has now been adopted by Australian Standards and International Standards Organisation, and being based on a radial or "star" configuration, allows all workstations to operate independently. A block diagram of a typical system of this type is shown at figure C2.

Figure C2

Figure C2: Star communications cabling

This type of medium is now becoming the standard for workstation cabling. Being only a relatively recent innovation, it is unlikely that any existing buildings in excess of 5 years old would be able to meet current standards.

Backbone cabling

Until recently, backbone cabling between major communications nodes within a building consisted of multicore twisted pair voice and coaxial data cabling, as is the case at the Port Adelaide College. However, in newer installations, the trend as prices drop is to the use of fibre optic cable due to higher transmission rates, band widths and noise reduction. Such backbone cabling is to be provided to the Onkaparinga Institute of Vocational Education Noarlunga campus, for which construction is about to be commenced.

Whether in copper or fibre optic cable. transmission links are installed as radial lines, or in a star topology, from the voice and/or data Communications Centre to communications closets strategically located in work areas. These closets house the active equipment necessary for communication with the workstations and also plug in patch panels to enable allocation of any workstation outlet to any Communications Centre port. This equipment is generally rack mounted to facilitate additions and alterations.

In the case of South Australian Colleges, the use of Synoptics Hubs and Cisco Routers has been adopted as being best suited to the operating environment of the user groups. This equipment has proven to be both reliable and cost effective over time and copes well for a system which is distributed both within campus areas and across the state using Telecom land lines.

Data traffic for Administration and Educational functions has been deliberately separated over the backbone cabling and hubs to minimise congestion and increase security. However, by the use of patch panels, any communications workstation outlet can be assigned to either Administration or Educational use.

Facilities are also available for access to centralised data processing facilities by remote or "home station" users by use of a personnel computer and modem link. This allows students (and staff) access to data from any location provided correct access codes are utilised. With the trend toward student learning independence, use of such facilities will almost certainly accelerate in the future.

Workstation cabling

Workstation cabling consists of 4 pair, unshielded twisted pair (UTP) copper conductor cabling terminated in keyed 8 pin RJ45 outlets as installed at the Port Adelaide College and proposed for the Onkaparinga Institute. In some electrically onerous environments, an overall shield may be applied for noise reduction. The RJ45 outlets are generally wall, service column or workstation mounted to enable plug in of user devices. Both voice and data outlets are identical, thereby enabling allocation of any workstation outlet to any communications function. By re-arrangement at the patch panel, the function of any outlet can be reallocated in seconds.

With advances in cable technology. UTP cables are now available which will operate at speeds up to 100 MHz, known as category 5 grade cables. The cost of this level of cable has now reduced to the point where the use of lower grade cables is not considered cost effective, particularly with respect to the capacity to cater for advances in computer technology.

Similarly, the initial cost to install a dense system of communications outlets is low compared with retrofitting of additional outlets in a facility. Consequently, the technique of "flood wiring" which provides at least 2 outlets to each potential workstation is becoming accepted practice, and has been generally adopted at both Port Adelaide and Onkaparinga campuses.

Development of infrared and radio communications to replace the need to plug in to wall outlets is proceeding, particularly for use with portable laptop computers. However, the number of devices which can simultaneously use such systems is currently limited due to interference problems. In addition, there are Occupational Health Safety and Welfare concerns associated with the use of radio frequency interfaces, similar to those presently being investigated with mobile telephones. It is therefore unlikely that any significant changes to present procedures will occur within at least the next 10 years with the exception of limited, special purpose applications.

An illustration of the power and communications facilities in a typical open plan room is shown at figure C3.

Figure C3

Figure C3: Typical room power and communications arrangement

System capacities and installation techniques

As with the Electrical Service systems described previously, the Communications System design must be such as to cater for both present needs and future upgrade paths, particularly within the backbone systems. Accordingly, for both the Port Adelaide and Onkaparinga facilities, both spare capacity and defined wiring corridors have been incorporated.

Present operating systems at Onkaparinga require 4 fibre optic cores for each of the Administration and Educational networks. Accordingly, 12 core fibre optic cables have been installed initially to provide 50% redundancy to cater tor expansion. Backbone cabling is installed on dedicated cable trays on well defined accessible routes between cable centres to facilitate the future installation of additional cabling if required. At least 100% spare cable tray capacity has been provided in each location.

Similarly, spare space is provided within the communications closets where the networking equipment and patch panels are housed. Initially, only one 18 inch rack, with an overall width of approximately 590 mm, is required at each location. The use of 1400 mm wide communications closets is now encouraged to enable future installation of an additional rack or system support equipment such as uninterruptible power supplies and line conditioners to enhance power supply reliability.

With respect to workstation cabling, which is necessarily hard wired from the communications centres, flood wiring is generally adopted to maximise flexibility. Nevertheless, if changes are required, replacement of portions of the workstation cabling will be necessary. Although unavoidable, the effect of this work on the building fabric will be minimised by adopting maximum use of ceiling space, demountable partitions, service columns, workstation ducts and skirting ducts to achieve simple, accessible wiring paths as described more fully in the Electrical Services portion of this paper.

Summary

The Australian and International communications standards are rapidly approaching a common base which will see the almost universal use of fibre optic backbone cabling, and UTP workstation cabling, terminated at RJ45 patch panels and workstation outlets.

Maximum accessibility for additional wiring and the initial provision of redundancy will ensure the installation of additional and modification of existing cabling without undue imposition.

This trend will allow the installation of system independent cabling which will remain valid for at least the next 15-20 years.

Author: Henrique J Harding, Bestec Pty Ltd. 144 Gawler Place, Adelaide SA 5000.

Please cite as: Harding, H. J. (1994). The built technology of the learning environment. In J. Steele and J. G. Hedberg (eds), Learning Environment Technology: Selected papers from LETA 94, 81-91. Canberra: AJET Publications. http://www.aset.org.au/confs/edtech94/ak/harding.html


[ EdTech'94 contents ] [ ASET Confs ]
This URL: http://www.aset.org.au/confs/edtech94/ak/harding.html
Last revised 27 May 2003. HTML editor: Roger Atkinson
Previous URL 8 May 1999 to 30 Sep 2002: http://cleo.murdoch.edu.au/aset/confs/edtech94/ak/harding.html